T90 Nylon/TWN75 600 Volts 90C Copper

Single copper conductor with thin wall PVC insulation and nylon covering. Rated 600 volts, and FT1.

CSA Spec C22.2 No. 75-M1983

Applications:

ECS
Catalogue
Number
Conductor Insulation
(inches)
Nylon
(inches)

Ampacity

(30C Ambient)
(amps)

Free Air

Damp/Dry

Ampacity

(30C Ambient)
(amps)

Conduit#

Damp/Dry

Ampacity

(30C Ambient)
(amps)

Free Air

Wet

Ampacity

(30C Ambient)
(amps)

Conduit#

Wet

Nominal
O.D.
(inches)
Total
Weight
(lbs/km)
No. AWG
Size
Stranding
TH14SL 1 14 Solid .015 .004 20 15 20 15 .11 49
TH12SL 1 12 Solid .015 .004 25 20 25 20 .12 76
TH10SL 1 10 Solid .020 .004 40 30 40 30 .15 121
TH14ST 1 14 19 Strand .015 .004 20 15 20 15 .11 53
TH12ST 1 12 19 Strand .015 .004 25 20 25 20 .13 79
TH10ST 1 10 19 Strand .020 .004 40 30 40 30 .17 128
TH08ST 1 8 19 Strand .030 .005 70 45 65 45 .22 213
TH06ST 1 6 19 Strand .030 .005 100 65 95 65 .26 322
TH04ST 1 4 19 Strand .040 .006 135 85 125 85 .33 515
TH03ST 1 3 19 Strand .040 .006 155 105 145 100 .36 633
TH02ST 1 2 19 Strand .040 .006 180 120 175 115 .39 787
TH01ST 1 1 19 Strand .050 .007 210 140 195 130 .45 994
TH001ST 1 1/0 19 Strand .050 .007 245 155 230 150 .49 1,234
TH002ST 1 2/0 19 Strand .050 .007 285 185* 265 175 .53 1,532
TH003ST 1 3/0 19 Strand .050 .007 330 210 310 200 .58 1,906
TH004ST 1 4/0 19 Strand .050 .007 385 235 360 230 .64 2,375
TH250ST 1 250 37 Strand .060 .008 425 265 405 255 .71 2,821
TH300ST 1 300 37 Strand .060 .008 480 295 445 285 .76 3,353
TH350ST 1 350 37 Strand .060 .008 530 325 505 310 .81 3,889
TH400ST 1 400 37 Strand .060 .008 575 345 545 335 .85 4,413
TH500ST 1 500 37 Strand .060 .008 660 395 620 380 .94 5,473
TH600ST 1 600 61 Strand .070 .009 740 455 695 427 1.04 6,584
TH750ST 1 750 61 Strand .070 .009 845 500 795 488 1.14 8,192

 

Colours: Standard colours are available.

*T90/TWN75 is NOT sunlight resistant.

 

# Based on not more than 3 copper conductors in raceway or cable.

 

*For 3-wire 120/240 and 120/208V residential services or sub-services, the allowable ampacity for #2/0 AWG copper shall be 200 amperes. In these cases, the 5% adjustment per C.E. Code Rule 8-106(1) cannot be applied.

 

Applications:

General purpose building wire for installation as exposed or concealed wiring and in raceways (except cable troughs) in dry or damp locations.
Minimum recommended installation temperature minus 10C (with suitable handling procedures).
Maximum conductor temperature 90C dry, 75C in wet locations, and 60C when exposed to oil.
Approved for use with ceiling fixtures.